Battery Overview
| NextCell 12V 100Ah LiFePO4 | 12.8 V · 1.28 kWh |
| NextCell 24V 100Ah LiFePO4 | 25.6 V · 2.56 kWh |
| NextCell 24V 100Ah Rack-Mounted LiFePO4 | 25.6 V · 2.56 kWh |
| NextCell 48V 100Ah LiFePO4 | 51.2 V (16S1P LiFePO4) · 5.12 kWh |
Troubleshooting
| Battery voltage < 21.6 V | Over-discharged. Charge at 0.05C with a 28.8 V charger until the pack has recovered. |
| High temperature (> 60 °C) or low temperature (< 0 °C) | The BMS halts charging/discharging until the unit returns to 0 °C–50 °C. |
| High current (> 2.2× rated current) | Reduce the inverter load. |
| Overvoltage (> 29.2 V) | Check the inverter charge voltage profile — set it to 28.8 V max. |
Voltage thresholds apply to the 24V pack.
Emergency & Safety Rules
- Fire: NEVER use water. Use ONLY a CO2 extinguisher or a fire blanket.
- Water / Flood: Disconnect at the inverter side. Do not touch wet equipment.
- Grounding: Earthing resistance must be less than 0.1 Ω.
- Storage: Recharge every 6 months to ≥ 90% SOC. Recharge within 12 hours after a full discharge.
Warranty
5-Year Limited Manufacturer Warranty (covering ≥ 4,000 cycles). Requires professional installation and COC compliance.