Installation Guide
Wiring Instructions
- Switch off the inverter, the battery breaker and all PV / AC inputs before starting.
- Mount the battery on a solid, dry wall away from direct sun and heat sources.
- Connect the battery positive (+) to the inverter battery positive and negative (−) to negative, using correctly rated cable and a DC breaker/fuse. Double-check polarity.
- For parallel systems (48V), use equal-length cables and connect to a common busbar.
- Connect the earth point to the installation earth (resistance < 0.1 Ω).
- Set the inverter battery type to LiFePO4 and the charge voltage within the battery's charge cut-off.
- Switch on the battery breaker, then the inverter. Confirm voltage and state of charge on the LCD.
[ PV / Grid ] ──► [ INVERTER ] ──► [ Home loads ]
│ ▲
(+) red │ │ (−) black
▼ │
[ DC BREAKER ]
│
[ NEXTCELL BATTERY ] ── earth (< 0.1 Ω)Installation must be done by a qualified professional with a valid Certificate of Compliance (COC).
Key Electrical Limits
| 12V · Charge Cut-off (manual-stated) | 14.6 V |
| 12V · Discharge Cut-off (manual-stated) | 8.2 V |
| 12V · Max Charge Current | 100 A |
| 12V · Max Continuous Discharge | 120 A |
| 24V · Charge Cut-off | 28.8 V |
| 24V · Discharge Cut-off | 18.4 V |
| 24V · Max Charge Current | 100 A |
| 24V · Max Continuous Discharge | 120 A |
| 48V · Charge Cut-off | 57.6 V |
| 48V · Discharge Cut-off | 36.8 V |
| 48V · Max Continuous Discharge | 120 A |
Inverter Compatibility
Sunsynk · Deye · Victron · Luxpower · Growatt · Voltronic
Safety
- Fire: NEVER use water. Use ONLY a CO2 extinguisher or a fire blanket.
- Water / Flood: Disconnect at the inverter side. Do not touch wet equipment.
- Grounding: Earthing resistance must be less than 0.1 Ω.
- Storage: Recharge every 6 months to ≥ 90% SOC. Recharge within 12 hours after a full discharge.